10 Diagnosis, Asset Management and service

VEGAPULS 63 • Modbus and Levelmaster protocol

41364-EN-130228

The below tables show typical examples of application-related meas-

urement errors with liquids. The measurement errors are differentiated

according to the following:

Constant level

Filling

Emptying

The images in column "Error pattern" show the real level with a bro-

ken line and the level displayed by the sensor as a continuous line.

1

2

Level

time

0

1 Real level

2 Level displayed by the sensor

Instructions:

Wherever the sensor displays a constant value, the reason could

also be the fault setting of the current output to "Hold value"

In case of a too low level indication, the reason could be a line

resistance that is too high

Measurement error with constant level

Fault description

Error pattern

Cause

Rectification

1. Measured value

shows a too low or too

high level

Level

time

0

– Min./max. adjustment not

correct

– Adapt min./max. adjustment

– Wrong linearization curve

– Adapt linearization curve

– Installation in a bypass tube or

standpipe, hence running time

error (small measurement error

close to 100 %/large error close

to 0 %)

– Check parameter "Application"

with respect to vessel form,

adapt if necessary (bypass,

standpipe, diameter)

2. Measured value

jumps towards 0 %

Level

time

0

– Multiple echo (vessel top,

product surface) with amplitude

higher than the level echo

– Check parameter "Application",

especially vessel top, product

type, dished end, high dielectric

figure, adapt if necessary

3. Measured value

jumps towards 100 %

Level

time

0

– Due to the process, the ampli-

tude of the product echo sinks

– A false signal suppression was

not carried out

– Carry out false signal suppres-

sion

– Amplitude or position of a

false echo has changed (e.g.

condensation, buildup); false

signal suppression no longer

matches

– Determine the reason for the

changed false signals, carry out

false signal suppression, e.g.

with condensation

Treatment of measure-

ment errors with liquids