9 Diagnostics and service
VEGAFLEX 81 • Foundation Fieldbus
44215-EN-130910
Code
Text mes-
sage
Cause
Rectification
S600
Unpermissi-
ble electronics
temperature
– Temperature of the pro-
cessing electronics in the
non-specified section
– Check ambient temperature
– Isolate electronics
– Use instrument with higher
temperature range
S601
Overfilling
– Level echo in the close
range not available
– Reduce level
– 100 % adjustment: Increase
value
– Check mounting socket
– Remove possible interfering
signals in the close range
– Use coaxial probe
S602
Level with-
in the search
range, com-
pensation
echo
– Compensation echo super-
imposed by medium
– 100 % adjustment: Increase
value
S603
Impermissi-
ble operating
voltage
– Operating voltage below
specified range
– Check electrical connection
– if necessary, increase
operating voltage
The following table shows the error codes and text messages in the
status message "Maintenance" and provides information on causes
as well as corrective measures.
Code
Text mes-
sage
Cause
Rectification
M500
Error in the
delivery sta-
tus
– With the reset to delivery
status, the data could not
be restored
– Repeat reset
– Load XML file with sensor
data into the sensor
M501
Error in the
non-active
linearization
table
– Hardware error EEPROM
– Exchanging the electronics
– Send instrument for repair
M502
Error in the
event memory
– Hardware error EEPROM
– Exchanging the electronics
– Send instrument for repair
M503
Reliability too
low
– Measurement certainty is
too low for a reliable meas-
urement
– Process component or
probe contaminated or
defective
– Check installation and
process conditions
– Clean or exchange process
component or probe
Maintenance