beautypg.com

VEGA VEGAFLEX 81 Foundation Fieldbus Coax probe User Manual

Page 38

background image

38

6 Set up with the display and adjustment module

VEGAFLEX 81 • Foundation Fieldbus

44215-EN-130910

Caution:

With active PIN, adjustment via PACTware/DTM as well as other

systems is also blocked.
You can change the PIN number under "Additional adjustments -

PIN".

In the main menu point "Display", the individual submenu points

should be selected subsequently and provided with the correct

parameters to ensure the optimum adjustment of the display options.

The procedure is described in the following.
The following submenu points are available:

The submenu points described below.

This menu item enables the setting of the requested national lan-

guage.

In the delivery status, the sensor is set to the ordered national lan-

guage.

In this menu item, you define the indication of the measured value

on the display. You can display two different measured values. In this

menu item, you define measured value 1.

The default setting for the displayed value 1 is "Filling height Level".

In this menu item, you define the indication of the measured value

on the display. You can display two different measured values. In this

menu item, you define measured value 2.

The default setting for the displayed value 2 is the electronics tem-

perature.

The optionally integrated background lighting can be adjusted via the

adjustment menu. The function depends on the height of the supply

voltage, see "Technical data".

Display

Display - Menu language

Display - Displayed value

1

Display - Displayed value

2

Display - Backlight