VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) Foundation Fieldbus Approval according to LPR radio standard User Manual

Page 65

background image

Input variable

Measured variable

The measured quantity is the distance between
process fitting of the sensor and product surface.
The reference plane is the seal surface on the
hexagon or the lower side of the flange.

3

4

2

1

Fig. 47: Data of the input variable

1

Reference plane

2

Measured variable, max. measuring range

3

Antenna length

4

Useful measuring range

Max. measuring range

35 m (114.83 ft)

Output variable

Output

-

Signal

digital output signal, Foundation Fieldbus protocol

-

Physical layer

according to IEC 61158-2

Damping (63 % of the input variable)

0 … 999 s, adjustable

Channel Numbers

-

Channel 1

Primary value

-

Channel 2

Secondary value 1

-

Channel 3

Secondary value 2

Transmission rate

31.25 Kbit/s

Current value

-

Non-Ex and Ex ia instrument

10 mA, ±0.5 mA

-

Ex d instruments

16 mA, ±0.5 mA

Resolution, digital

> 1

mm (0.039 in)

VEGAPULS

62 • Approval according to LPR radio standard

65

11 Supplement