VEGA VEGAMIP R62 Receiving unit - Relay User Manual

Page 31

background image

Level

Switching status

Signal lamp - Re-
lay (yellow)

Mode min.
Dry run protection

5

3

4

(8)

(6)

(7)

Relay deenergized

Failure of the supply
voltage
(max./min. mode)

any

5

3

4

(8)

(6)

(7)

Relay deenergized

Malfunction

any

5

3

4

(8)

(6)

(7)

Relay deenergized

Red failure LED

lights

By means of the slide switch, you can set the switching direction
according to the switching function your relay output should perform.

l

For maximum indication or overfill protection set the slide switch to
position max.

l

For minimum indication or dry run protection, set the slide switch to
position min.

The relay is energized if the yellow relay control lamp lights.

With the two keys you can change the LED indication strip and adjust
the switching point to the medium.

The keys are lowered to avoid unintentional changes of the setting. For
adjustment, use for example, a small screwdriver.

If you press one of the keys for more than two seconds, the adjustment
range shifts automatically in the respective direction. The greater the
distance between emitting and receiving unit, the greater the adjust-
ment range of the indication. The LED indication strip always shows a
small section of the actual measuring range.

Pressing the "<--" key makes the sensor more sensitive. Pressing the
"

-->" key makes the sensor less sensitive.

Sensitivity adjustment

VEGAMIP R

62 • - Relay

31

6 Setup

41912

-

EN

-120228