VEGA VEGAMIP R62 Receiving unit - Relay User Manual
Page 24
4
Insert the cable into the sensor through the cable entry
Fig. 16: Connection steps 4 and 5
5
Insert the wire ends into the terminals according to the wiring plan
Information:
Solid cores as well as flexible cores with cable end sleeves are
inserted directly into the terminal openings. In case of flexible cores
without end sleeves, press the terminal with a small screwdriver; the
terminal opening is freed. When the screwdriver is released, the
terminal closes again.
6
Check the hold of the wires in the terminals by lightly pulling on
them
7
Connect the screen to the internal ground terminal, connect the
outer ground terminal to potential equalisation
8
Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable
9
Screw the housing cover back on
The electrical connection is finished.
Information:
The terminal block is pluggable and can be removed from the
electronics. To do this, lift the terminal block with a small screwdriver
and pull it out. When inserting the terminal block again, you should
hear it snap in.
Proceed as follows:
1
Loosen the four screws on the housing socket with an Allen key
Connection steps - ex-
ternal housing
24
VEGAMIP R
62 • - Relay
5 Connecting to power supply