VEGA VEGABAR 83 4 … 20 mA - Operating Instructions User Manual

Page 62

background image

62

11 Supplement

VEGABAR 83 • 4 … 20 mA

45033-EN-131010

Medium or ambient tempera-

ture T

Accuracy class 0.1 %

Accuracy class 0.2 %

100 … 120 °C (+212 … +248 °F)

< {0.15 % + 0.005 %/K x (T -

100 °C)} x {0.5+0.5 x TD}

< {0.40 % + 0.01 %/K x (T - 100 °C)}

x {0.5+0.5 x TD}

Ceramic/Metal measuring cell - climate-compensated
Compensated temperature range

0 … +100 °C (+32 … +212 °F)

Non-compensated temperature range

-40 … 0 °C (-40 … +32 °F), -100 … 130 °C

(212 … +276 °F)

Nominal measuring range in bar/

kPa

Nominal measuring

range in psig

In the compensated

temperature range

In the non-compen-

sated temperature

range

0 … 10 bar/0 … 1000 kPa

0 … 150 psig

< {0.05 % + 0.1 x

(0.5+0.5 x TD)}

< {0.1 % + 0.15 x

(0.5+0.5 x TD)}

0 … 25 bar/0 … 2500 kPa

0 … 350 psig

-1 … 0 bar/-100 … 0 kPa

-15 … 0 psig

-1 … 1.5 bar/-100 … 150 kPa

-15 … 25 psig

-1 … 10 bar/-100 … 1000 kPa

-15 … 150 psig

-1 … 25 bar/-100 … 2500 kPa

-15 … 350 psig

0 … 1 bar/0 … 100 kPa

0 … 15 psig

< {0.1 % + 0.2 x

(0.5+0.5 x TD)}

< {0.1 % + 0.3 x

(0.5+0.5 x TD)}

0 … 2.5 bar/0 … 250 kPa

0 … 35 psig

-0.5 … 0.5 bar/-50 … 50 kPa

-7 … 7 psig

-0.2 … 0.2 bar/-20 … 20 kPa

-3 … 3 psig

< {0.15 % + 0.4 x

(0.5+0.5 x TD)}

< {0.15 % + 0.6 x

(0.5+0.5 x TD)}

0 … 0.4 bar/0 … 40 kPa

0 … 6 psig

Thermal change, current output
Applies also to the analogue 4 … 20 mA current output and refers to the set span.
Thermal change, current output

< 0.05 %/10 K, max. < 0.15 %, each with -40 … +80 °C

(-40 … +176 °F)

0,15 %

-0,15 %

-40°C

-20°C

20°C

40°C

60°C

80°C

Fig. 31: Thermal change, current output