beautypg.com

VEGA VEGABAR 83 4 … 20 mA - Operating Instructions User Manual

Page 36

background image

36

6 Set up with the display and adjustment module

VEGABAR 83 • 4 … 20 mA

45033-EN-131010

In this menu item, the device status is displayed.

The respective min. and max. measured value is saved in the sensor.

The two values are displayed in the menu item "Peak values, pres-

sure".
In another window you can carry out a reset of the peak values

separately.

The respective min. and max. measured values of the measuring cell

and electronics temperature are stored in the sensor. In the menu

item "Peak value, temperature", both values are displayed.
In another window you can carry out a reset of the two peak values

separately.

In this menu item you can simulate measured values via the current

output. This allows the signal path to be tested, e.g. via downstream

indicating instruments or the input card of the control system.

Select the requested simulation size and adjust the requested value.
Caution:

During simulation, the simulated value is outputted as 4 … 20 mA cur-

rent value and digital HART signal.
Push the [ESC] key to deactivate the simulation.
Information:

The simulation is terminated automatically 60 minutes after the last

key has been pushed.

By entering a 4-digit PIN, you protect the sensor data against unau-

thorized access and unintentional modification.

Diagnostics - Device

status

Diagnostics - Peak val-

ues, pressure

Diagnostics - Peak val-

ues, temperature

Diagnosis - Simulation

Additional settings - PIN