6 Set up with the display and adjustment module
VEGABAR 83 • 4 … 20 mA
45033-EN-131010
In this menu item, the device status is displayed.
The respective min. and max. measured value is saved in the sensor.
The two values are displayed in the menu item "Peak values, pres-
sure".
In another window you can carry out a reset of the peak values
separately.
The respective min. and max. measured values of the measuring cell
and electronics temperature are stored in the sensor. In the menu
item "Peak value, temperature", both values are displayed.
In another window you can carry out a reset of the two peak values
separately.
In this menu item you can simulate measured values via the current
output. This allows the signal path to be tested, e.g. via downstream
indicating instruments or the input card of the control system.
Select the requested simulation size and adjust the requested value.
Caution:
During simulation, the simulated value is outputted as 4 … 20 mA cur-
rent value and digital HART signal.
Push the [ESC] key to deactivate the simulation.
Information:
The simulation is terminated automatically 60 minutes after the last
key has been pushed.
By entering a 4-digit PIN, you protect the sensor data against unau-
thorized access and unintentional modification.
Diagnostics - Device
status
Diagnostics - Peak val-
ues, pressure
Diagnostics - Peak val-
ues, temperature
Diagnosis - Simulation
Additional settings - PIN