beautypg.com

2 parameter adjustment with pactware – VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART - two-wire Approval according to LPR radio standard User Manual

Page 52

background image

Note:
With power supply units with integrated HART resistance (internal
resistance approx. 250 Ω), an additional external resistance is not
necessary. This applies, e.g. to the VEGA instruments VEGATRENN
149A, VEGAMET 381, VEGAMET 391. Common Ex separators are
also usually equipped with a sufficient current limitation resistance. In
such cases, the interface converter can be connected parallel to the
4 … 20 mA cable (dashed line in the previous illustration).

7

.2 Parameter adjustment with PACTware

For parameter adjustment of the sensor via a Windows PC, the
configuration software PACTware and a suitable instrument driver
(DTM) according to FDT standard are required. The up-to-date
PACTware version as well as all available DTMs are compiled in a
DTM Collection. The DTMs can also be integrated into other frame
applications according to FDT standard.

Note:
To ensure that all instrument functions are supported, you should
always use the latest DTM Collection. Furthermore, not all described
functions are included in older firmware versions. You can download
the latest instrument software from our homepage. A description of the
update procedure is also available in the Internet.

Further setup steps are described in the operating instructions manual
"DTM C

ollection/PACTware" attached to each DTM Collection and

which can also be downloaded from the Internet. Detailed descriptions
are available in the online help of PACTware and the DTMs.

Fig. 34: Example of a DTM view

Prerequisites

52

VEGAPULS

61 • Approval according to LPR radio standard

7 Setup with PACTware

41713

-EN

-120301