Abb total flow, Wiring plan, Parameter – VEGA VEGAFLEX 86 Modbus and Levelmaster protocol Coax probe User Manual

Page 82: 11 supplement

background image

82

11 Supplement

VEGAFLEX 86 • Modbus and Levelmaster protocol

42288-EN-130314

The basic number of the input registers is always added to the input register address of VEGAFLEX

86.
Address 1300 must hence be entered as register address for RTU Fisher ROC 809.

ABB Total Flow

Wiring plan

+

+

power supply

MODBUS

D0

D1

IS GND

USB

1

2

13

45

2o

ff

on

( )

(

)

(-)

(-)

8

1

2

6

7

Bus +

Bus -

GND

VBAT

Fig. 39: Connection of VEGAFLEX 86 to RTU ABB Total Flow
1 VEGAFLEX 86

2 RTU ABB Total Flow

Parameter

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

16 Bit Modicon

Input Register Base Number

1

The basic number of the input registers is always added to the input register address of VEGAFLEX

86.
Address 1303 must hence be entered as register address for 1302 for RTU ABB Total Flow.