beautypg.com

Set baud rate, Set receive to transmit delay, Report number of floats – VEGA VEGAFLEX 86 Modbus and Levelmaster protocol Coax probe User Manual

Page 80: Report receive to transmit delay

background image

80

11 Supplement

VEGAFLEX 86 • Modbus and Levelmaster protocol

42288-EN-130314

Set Baud Rate

Request:

Parameter

Length

Code/Data

Set Baud Rate

8 (12) characters ASCII

UuuBbbbb[b][pds]
Bbbbb[b] = 1200, 9600 (default)
pds = parity, data length, stop bit

(optional)
parity: none = 81, even = 71 (de-

fault), odd = 71

Response:

Parameter

Length

Code/Data

Set Baud Rate

11 characters ASCII

Example: U01B9600E71
Change instrument on address 1 to baudrate 9600, parity even, 7 data bits, 1 stop bit

Set Receive to Transmit Delay

Request:

Parameter

Length

Code/Data

Set Receive to Transmit Delay

7 characters ASCII

UuuRmmm
mmm = milliseconds (50 up to 250),

default = 127 ms

Response:

Parameter

Length

Code/Data

Set Receive to Transmit Delay

6 characters ASCII

UuuROK

Report Number of Floats

Request:

Parameter

Length

Code/Data

Set Receive to Transmit Delay

4 characters ASCII

UuuF

Response:

Parameter

Length

Code/Data

Set Receive to Transmit Delay

5 characters ASCII

UuuFn
n = number of measurement values

(0, 1 or 2)

Report Receive to Transmit Delay

Request:

Parameter

Length

Code/Data

Report Receive to Transmit Delay

4 characters ASCII

UuuR