beautypg.com

Assign unit number, Set number of floats, Set baud rate – VEGA VEGAFLEX 83 Modbus and Levelmaster protocol PFA insulated User Manual

Page 82

background image

82

11 Supplement

VEGAFLEX 83 • Modbus and Levelmaster protocol

41838-EN-130314

Response:

Parameter

Length

Code/Data

Report Level (and Temperature)

6 characters ASCII

UuuNnn

Assign Unit Number

Request:

Parameter

Length

Code/Data

Assign Unit Number

6 characters ASCII

UuuNnn

Response:

Parameter

Length

Code/Data

Assign Unit Number

6 characters ASCII

UuuNOK
uu = new Address

Set number of Floats

Request:

Parameter

Length

Code/Data

Set number of Floats

5 characters ASCII

UuuFn

Response:

Parameter

Length

Code/Data

Set number of Floats

6 characters ASCII

UuuFOK

If the number is set to 0, no level is returned

Set Baud Rate

Request:

Parameter

Length

Code/Data

Set Baud Rate

8 (12) characters ASCII

UuuBbbbb[b][pds]
Bbbbb[b] = 1200, 9600 (default)
pds = parity, data length, stop bit

(optional)
parity: none = 81, even = 71 (de-

fault), odd = 71

Response:

Parameter

Length

Code/Data

Set Baud Rate

11 characters ASCII

Example: U01B9600E71
Change instrument on address 1 to baudrate 9600, parity even, 7 data bits, 1 stop bit