6 Set up with the display and adjustment module

VEGAFLEX 83 • Modbus and Levelmaster protocol

41838-EN-130314

Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. The distance refers to the sensor

reference plane (seal surface of the process fitting). Keep in mind that

the max. level must lie below the dead band.
Min. adjustment

In this menu item, you can enter the min. adjustment for the level.
Enter the suitable distance value in m for the empty vessel (e.g.

distance from the flange to the probe end) corresponding to the per-

centage value. The distance refers tot he sensor reference plane (seal

surface of the process fitting).

Dielectric constant - upper medium

In this menu item, you can define the medium type (product).
Max. adjustment

In this menu item, you can enter the max. adjustment for the level.
Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. The distance refers to the sensor

reference plane (seal surface of the process fitting). Keep in mind that

the max. level must lie below the dead band.
Min. adjustment

In this menu item, you can enter the min. adjustment for the level.
Enter the suitable distance value in m for the empty vessel (e.g.

distance from the flange to the probe end) corresponding to the per-

centage value. The distance refers tot he sensor reference plane (seal

surface of the process fitting).

Max. adjustment - Interface

Carry out the max. adjustment for the interface.
To do this, enter the percentage value and the suitable distance value

in m for the full vessel.
Min. adjustment - Interface

Carry out the min. adjustment for the interface.
To do this, enter the percentage value and the suitable distance value

in m for the empty vessel.

Interface measurement