beautypg.com

Quick start – VEGA VEGAFLEX 83 Modbus and Levelmaster protocol PFA insulated User Manual

Page 2

background image

2

Quick start

VEGAFLEX 83 • Modbus and Levelmaster protocol

41838-EN-130314

Quick start

The quick start procedure enables a quick setup with many applica-

tions. You can find further information in the respective chapters of the

operating instructions manual.
1. Distance from the metallic vessel wall > 300 mm. Distance from

non-metallic vessel wall > 500 mm. The probe must not touch any

installations or the vessel wall.

2. Place a metal sheet beneath the process fitting with non-metal

vessels.

1

2

Fig. 1: Installation in plastic silo
1 Flange

2 Metal sheet

3. If necessary, fasten probe end.
For further information see chapter "Mounting".
1. Make sure that the power supply corresponds to the specifica-

tions on the type label.

2. Connect the instrument according to the following illustration

+

+

power supply

MODBUS

D0

D1

IS GND

USB

1

2

1

3

4

5

2

off on

( )

(

)

(-)

(-)

Fig. 2: Connection compartment
1 USB connection

2 Slide switch for integrated termination resistor (120 Ω)

For further information see chapter "Connecting to power supply".

For standard applications we recommend selecting the "Quick setup"

in the display and adjustment module.

Mounting

Electrical connection

Set parameters