VEGA VEGAFLEX 83 Modbus and Levelmaster protocol PFA insulated User Manual
Page 33
33
6 Set up with the display and adjustment module
VEGAFLEX 83 • Modbus and Levelmaster protocol
41838-EN-130314
Enter the suitable distance value in m for the empty vessel (e.g.
distance from the flange to the probe end) corresponding to the per-
centage value. The distance refers tot he sensor reference plane (seal
surface of the process fitting).
This menu item is only available if you have selected interface meas-
urement under the menu item "Application".
You can accept the adjustment of the level measurement also for the
interface measurement. If you select "Yes", the current setting will be
displayed.
If you have selected "No", you can enter the adjustment for the inter-
face separately. Enter the requested percentage value.
For the full vessel, enter the distance value in m matching the per-
centage value.
This menu item is only available if you have selected interface meas-
urement under the menu item "Application". If you have selected "Yes"
in the previous menu item (accept adjustment of the level measure-
ment), the current setting will be displayed.
If you have selected "No", you can enter the adjustment for the inter-
face measurement separately.
Setup - Max. adjustment -
Interface
Setup - Min. adjustment -
Interface