beautypg.com

5 set receive to transmit delay, 5 report number of floats, 5 report receive to transmit delay – VEGA VEGAPULS 68 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual

Page 76: 5 error codes

background image

76

11 Supplement

VEGAPULS 68 • Modbus and Levelmaster protocol

41370-EN-121011

Response:

Parameter

Length

Code/Data

Set Baud Rate

11 characters ASCII

Example: U01B9600E71
Change instrument on address 1 to baudrate 9600, parity even, 7 data bits, 1 stop bit

11.5 Set Receive to Transmit Delay

Request:

Parameter

Length

Code/Data

Set Receive to Transmit Delay

7 characters ASCII

UuuRmmm
mmm = milliseconds (50 bis 250),

default = 127 ms

Response:

Parameter

Length

Code/Data

Set Receive to Transmit Delay

6 characters ASCII

UuuROK

11.5 Report Number of Floats

Request:

Parameter

Length

Code/Data

Set Receive to Transmit Delay

4 characters ASCII

UuuF

Response:

Parameter

Length

Code/Data

Set Receive to Transmit Delay

5 characters ASCII

UuuFn
n = number of measurement values

(0, 1 or 2)

11.5 Report Receive to Transmit Delay

Request:

Parameter

Length

Code/Data

Report Receive to Transmit Delay

4 characters ASCII

UuuR

Response:

Parameter

Length

Code/Data

Report Receive to Transmit Delay

7 characters ASCII

UuuRmmm
mmm = milliseconds (50 bis 250),

default = 127 ms

11.5 Error codes

Error Code

Name

EE-Error

Error While Storing Data in EEPROM

FR-Error

Erorr in Frame (to short, to long, wrong data)