5 report unit number, 5 assign unit number, 5 set number of floats – VEGA VEGAPULS 68 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual
Page 75: 5 set baud rate

75
11 Supplement
VEGAPULS 68 • Modbus and Levelmaster protocol
41370-EN-121011
SV as second measured value.
PV, SV, TV and QV can be adjusted via the sensor DTM.
11.5 Report Unit Number
Request:
Parameter
Length
Code/Data
Report Unit Number
5 characters ASCII
U**N?
Response:
Parameter
Length
Code/Data
Report Level (and Temperature)
6 characters ASCII
UuuNnn
11.5 Assign Unit Number
Request:
Parameter
Length
Code/Data
Assign Unit Number
6 characters ASCII
UuuNnn
Response:
Parameter
Length
Code/Data
Assign Unit Number
6 characters ASCII
UuuNOK
uu = new Address
11.5 Set number of Floats
Request:
Parameter
Length
Code/Data
Set number of Floats
5 characters ASCII
UuuFn
Response:
Parameter
Length
Code/Data
Set number of Floats
6 characters ASCII
UuuFOK
If the number is set to 0, no level is returned
11.5 Set Baud Rate
Request:
Parameter
Length
Code/Data
Set Baud Rate
8 (12) characters ASCII
UuuBbbbb[b][pds]
Bbbbb[b] = 1200, 9600 (default)
pds = parity, data length, stop bit
(optional)
parity: none = 81, even = 71 (de-
fault), odd = 71