3 modbus register, 2 parameters for the bus communication, 2 general configuration of the host – VEGA VEGAPULS 68 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual
Page 68: 3 holding register, 3 modbus register 11.3 holding register
68
11 Supplement
VEGAPULS 68 • Modbus and Levelmaster protocol
41370-EN-121011
RTU
Protocol
Bristol ControlWaveMicro
Modbus RTU, ASCII
Fisher ROC
Modbus RTU, ASCII
ScadaPack
Modbus RTU, ASCII
Thermo Electron Autopilot
Modbus RTU, ASCII
11.2 Parameters for the bus communication
The VEGAPULS 68 is preset with the default values:
Parameter
Configurable Values
Default Value
Baud Rate
1200, 2400, 4800, 9600, 19200
9600
Start Bits
1
1
Data Bits
7, 8
8
Parity
None, Odd, Even
None
Stop Bits
1, 2
1
Address range Modbus
1 … 255
246
Start bits and data bits cannot be modified.
11.2 General configuration of the host
The data exchange with status and variables between field device and host is carried out via
register. For this, a configuration in the host is required. Floating point numbers with short prevision
(4 bytes) according to IEEE 754 are transmitted with individually selectable order of the data bytes
(byte transmission order). This "Byte transmission order" is determined in the parameter "Format
Code". Hence the RTU knows the registers of the VEGAPULS 68 which must be contacted for the
variables and status information.
Format Code
Byte transmission order
0
ABCD
1
CDAB
2
DCBA
3
BADC
11.3 Modbus register
11.3 Holding Register
The Holding registers consist of 16 bit. They can be read and written. Before each command, the
address (1 byte), after each command, a CRC (2 byte) is sent.
Register Name Register Num-
ber
Type
Configurable
Values
Default Value
Unit
Address
200
Word
1 … 255
246
-
Baud Rate
201
Word
1200, 2400,
4800, 9600,
19200
9600
-