7 Set up with the display and adjustment module

FIBERTRAC 31 • 4 … 20 mA/HART - four-wire

43386-EN-131119

If the measured value is outputted via the 4 … 20 mA output, you

must not switch over to HART Multidrop.
The mode 'Standard', with fixed address 0 (factory setting), means

output of the measured value as 8/16 mA signal.
This parameter is described in the operating instructions manual

"Display and adjustment module".

With this function

Load parameter adjustment data from the sensor into the display

and adjustment module

Write parameter adjustment data from the display and adjustment

module into the sensor

This parameter is described in the operating instructions manual

"Display and adjustment module".
Info

In this menu you will find the following menu items:

Instrument name - shows instrument name and serial number

Instrument version - shows hardware and software version of the

instrument

Date of manufacture - shows calibration date and the date of the

last change

Instrument features - shows further instrument features

These parameters are described in the operating instructions manual

"Display and adjustment module".

7.6 Saving the parameter adjustment data

We recommended noting the adjusted data, e.g. in this operating

instructions manual, and archiving them afterwards. They are thus

available for multiple use or service purposes.
If the instrument is equipped with a display and adjustment module,

the data in the sensor can be saved in the display and adjustment

module. The procedure is described in the operating instructions

manual "Display and adjustment module" in the menu item "Copy

sensor data". The data remain there permanently even if the sensor

power supply fails.
The following data or settings for adjustment of the display and ad-

justment module are saved:

All data of the menu "Setup" and "Display"

In the menu "Additional adjustments" the items "Sensor-specific

units, temperature unit and linearization"

The values of the user programmable linearization curve

The function can also be used to transfer settings from one instru-

ment to another instrument of the same type. If it is necessary to

exchange a sensor, the display and adjustment module is inserted

into the replacement instrument and the data are likewise written into

the sensor via the menu item "Copy sensor data".

Additional adjustments -

Copy instrument settings

Info