Basic settings: Resetting of the parameter adjustments to default
values at the time of shipment. Order-specific settings are deleted.
Default settings: Resetting of the parameter adjustment like under
"Basic settings". In addition, special parameters are reset to default
values. Order-specific settings are deleted.
Peak values of measured value: Resetting of the parameter adjust-
ments in the menu item "Setup" to the default values of the respective
instrument. Order-specific settings remain but are not taken over into
the current parameters.
Peak values of temperature: Resetting of the measured min. and
max. temperatures to the actual measured value.
The following table shows the default values of the instrument. The
values apply for the application "Level". First of all you have to select
the application.
Depending on the instrument version, not all menu items may be
available or they may be differently assigned:
Menu
Menu item
Default value
Setup
Measurement
loop name
Sensor
Isotope
Cs-137
Application
Limit level
Adjustment mode Single point adjustment
Adjustment - un-
covered
90000 ct/s
Adjustment - cov-
ered
9000 ct/s
only with two-point adjustment
Delta I
90 %
Background ra-
diation
0 ct/s
Temperature unit °C
Damping
Is calculated automatically by the in-
strument
Current output
mode
8/16 mA, < 3.6 mA
Mode - Relay
Overfill protection
Block adjustment Released
Display
Language
Selected language
Displayed value
Pulse rate
Additional adjust-
ments
Temperature unit °C
HART mode
Standard
With this function you can select the mode.
The sensor offers the HART modes standard and multidrop.
Additional adjustments -
HART mode