9 Diagnosis, Asset Management and service
VEGAPULS 67 • HART - integrated accumulator
40795-EN-121011
Code
Text mes-
sage
Cause
Rectification
F261
Error in the
configuration
– Error during setup
– False signal suppression
faulty
– Error when carrying out a
reset
– Repeat setup
– Repeat reset
F264
Installation/
Setup error
– Adjustment not within the
vessel height/measuring
range
– Max. measuring range of
the instrument not sufficient
– Check or correct installation
and/or parameter adjust-
ment
– Use an instrument with big-
ger measuring range
F265
Measurement
function dis-
turbed
– Sensor no longer carries
out a measurement
– Operating voltage too low
– Check operating voltage
– Carry out a reset
– Separate operating voltage
briefly
The following table shows the error codes and text messages in the
status message "Function check" and provides information on causes
as well as corrective measures.
Code
Text mes-
sage
Cause
Rectification
C700
Simulation ac-
tive
– A simulation is active
– Finish simulation
– Wait for the automatic end
after 60 mins.
The following table shows the error codes and text messages in the
status message "Out of specification" and provides information on
causes as well as corrective measures.
Code
Text mes-
sage
Cause
Rectification
S600
Unpermissi-
ble electronics
temperature
– Temperature of the elec-
tronics in the non-specified
section
– Check ambient temperature
– Isolate electronics
– Use instrument with higher
temperature range
S601
Overfilling
– Danger of vessel overfilling
– Make sure that there is no
further filling
– Check level in the vessel
The following table shows the error codes and text messages in the
status message "Maintenance" and provides information on causes
as well as corrective measures.