VEGA VEGAPULS 67 (≥ 2.0.0 - ≥ 4.0.0) HART - integrated accumulator User Manual
Page 35
35
6 Set up with the indicating and adjustment module
VEGAPULS 67 • HART - integrated accumulator
40795-EN-121011
With this selection, the operating range of the sensor is adapted to
the vessel height and the reliability with different frame conditions is
increased considerably.
Independent from this, the min. adjustment must be carried out.
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Also the vessel form can influence the measurement apart from the
medium and the application. To adapt the sensor to these measure-
ment conditions, this menu item offers you different options for vessel
bottom and ceiling in case of certain applications.
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Since a radar sensor is a distance measuring instrument, the distance
from the sensor to the product surface is measured. For indication of
the real level, an allocation of the measured distance to the percent-
age height must be carried out.
To perform the adjustment, enter the distance with full and empty ves-
sel, see the following example:
Setup/Vessel height,
measuring range
Setup/Vessel form
Setup/Adjustment