VEGA VEGAPULS WL 61 Profibus PA User Manual
Page 28
28
7 Diagnosis, Asset Management and service
VEGAPULS WL 61 • Profibus PA
38062-EN-121011
The following table shows the codes and text messages in the status
message "Failure" and gives information on the reason and rectifica-
tion. Keep in mind that some specification are only valid for four-wire
instruments and the electronics with VEGAPULS WL 61 cannot be
exchanged by the user.
Code
Text mes-
sage
Cause
Rectification
PA DevS-
pec
Diagnosis
F013
no meas-
ured value
available
– Sensor does not
detect an echo during
operation
– Antenna system con-
taminated or defective
– Check or correct
installation and/or
parameter adjustment
– Clean or exchange
process component or
antenna
Bit 0
F017
Adjustment
span too
small
– Adjustment not within
specification
– Change adjustment
according to the limit
values (difference
between min. and
max. ≥ 10 mm)
Bit 1
F025
Error in the
lineariza-
tion table
– Index markers are not
continuously rising, for
examle unlogical value
pairs
– Check linearization
table
– Delete table/Create
new
Bit 2
F036
No op-
erable
software
– Failed or interrupted
software update
– Repeat software
update
– Check electronics
version
– Exchanging the elec-
tronics
– Send instrument for
repair
Bit 3
F040
Error in the
electronics
– Hardware defect
– Exchanging the elec-
tronics
– Send instrument for
repair
Bit 4
F080
– General software error
– Separate operating
voltage briefly
Bit 5
F105
Determine
measured
value
– The instrument is still
in the start phase, the
measured value could
not yet be determined
– Wait for the warm-up
phase
– Duration depending
on the version and
parameter adjustment
up to approximately
3 min.
Bit 6
F113
Communi-
cation error
– Error in the internal
instrument communi-
cation
– Separate operating
voltage briefly
– Send instrument for
repair
Bit 7
Failure (failure)