6 Set up

VEGAPULS WL 61 • Profibus PA

38062-EN-121011

6 Set up

6.1 DD adjustment programs

Device descriptions as Enhanced Device Description (EDD) are

available for DD adjustment programs such as, for example, AMS™

and PDM.
The files can be downloaded at www.vega.com/downloads under

"Software".

6.2 Adjustment

Since a radar sensor is a distance measuring instrument, the distance

from the sensor to the product surface is measured. For indication of

the real level, an allocation of the measured distance to the percent-

age height must be carried out. To perform the adjustment, enter the

distance with full and empty vessel, see the following example:

2

1

0,5 m (19.68

")

5 m

(196.85

")

100%

0%

Fig. 24: Parameterization example
1 Min. level = max. meas. distance

2 Max. level = min. meas. distance

If these values are not known, an adjustment with the distances of for

example 10 % and 90 % is possible. Starting point for these distance

specifications is always the seal surface of the thread or flange. By

means of these settings, the real level will be calculated.
The real product level during this adjustment is not important, be-

cause the min./max. adjustment is always carried out without chang-

ing the product level. These settings can be made ahead of time

without the instrument having to be installed.