4 Mounting

VEGAPULS WL 61 • Profibus PA

38062-EN-121011

Through the action of filling, stirring and other processes in the vessel,

compact foams that considerably damp the emitted signals may form

on the product surface.
If foams are causing measurement errors, the biggest possible radar

antennas, the electronics with increased sensitivity or low frequency

radar sensors (C band) should be used.
As an alternative, sensors with guided microwave can be used. These

are unaffected by foam generation and are best suited for such ap-

plications.

The short examples give you introductory information on the flow

measurement. Detailed planning information is available from flume

manufacturers and in special literature.

h

ma

x

d

mi

n

≥ 2 mm x h

ma

x

90°

4

3 ... 4 h

max

≥ 50 mm

90°

2

3

1

Fig. 21: Flow measurement with rectangular flume: d

min.

= min. distance of the

sensor (see chapter "Technical data"); h

max.

= max. filling of the rectangular

flume
1 Overflow orifice (side view)

2 Headwater

3 Tail water

4 Overfall orifice (view from bottom water)

In general, the following points must be observed:

Install the sensor on the headwater side

Installation in the centre of the flume and vertical to the liquid

surface

Distance to the overfall orifice

Distance of orifice opening above ground

Min. distance of the orifice opening to bottom water

Min. distance of the sensor to max. storage level

Foam generation

Flow measurement with

rectangular flume