11 Supplement
VEGAPULS 66 enamel • Profibus PA
36529-EN-121011
Electrical protective measures
Protection, depending on housing version
Ʋ Plastic housing
IP 66/IP 67
Ʋ Aluminium housing, stainless steel
housing - investment casting, stain-
less steel housing - electro-polished
IP 66/IP 68 (0.2 bar)
4)
Ʋ Aluminium and stainless housing, in-
vestment casting (optionally available)
IP 66/IP 68 (1 bar)
Overvoltage category
III
Protection class
III
Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments must be carefully noted.
They are part of the delivery or can be downloaded under www.vega.com and "VEGA Tools" as
well as under "Downloads" and "Approvals".
11.2 Communication Profibus PA
11.2 Instrument master file
The instrument master file (GSD) contains the characteristic data of the Profibus PA instrument.
These data are, e.g. the permissible transmission rates as well as information on diagnostics values
and the format of the measured value outputted by the PA instrument.
A bitmap file is also provided for the Profibus network planning tool. This file is installed automati-
cally when the GSD file is integrated. The bitmap file is used for symbolic indication of the PA instru-
ment in the configuration tool.
11.3 ID number
Each Profibus instrument gets an unambiguous ident number (ID number) from the Profibus user
organisation (PNO). This ID number is also included in the name of the GSD file. Optionally to this
manufacturer-specific GSD file, PNO provides also a general so-called profile-specific GSD file. If
the general GSD file is used, the sensor must be set to the profile-specific ident number via the DTM
software. By default, the sensor operates with the manufacturer-specific ID number. When using the
instruments on a segment coupler SK-2 or SK-3, no special GSD files are required.
The following table shows the instrument ID and the GSD names for the VEGAPULS radar sensors.
Device name
Instrument ID
GSD file name
VEGA
Instrument class in
profile 3.02
VEGA
Profile-specific
VEGAPULS WL 61
0x0CDB
0x9702
PS61WL0CDB.GSD PA139702.GSD
VEGAPULS 61
0x0BFC
0x9702
PS610BFC.GSD
PA139702.GSD
VEGAPULS 62
0x0BFD
0x9702
PS620BFD.GSD
PA139702.GSD
VEGAPULS 63
0x0BFE
0x9702
PS630BFE.GSD
PA139702.GSD
VEGAPULS 65
0x0BFF
0x9702
PS650BFF.GSD
PA139702.GSD
4)
The prerequisites for maintaining the protection rating are a suitable cable as well as correct mounting.