VEGA VEGAPULS 66 (≥ 2.0.0 - ≥ 4.0.0) enamel Profibus PA User Manual
Page 40
40
6 Set up with the indicating and adjustment module
VEGAPULS 66 enamel • Profibus PA
36529-EN-121011
The "Echo curve" shows the signal strength of the echoes over the
measuring range in dB. The signal strength enables an evaluation of
the quality of the measurement.
The "False signal suppression" displays the saved false echoes (see
menu "Additional settings") of the empty vessel with signal strength in
"dB" over the measuring range.
A comparison of echo curve and false signal suppression allows a
more accurate conclusion on measurement reliability. The selected
curve is continuously updated. With the [OK] key, a submenu with
zoom functions is opened:
•
"X-Zoom": Zoom function for the meas. distance
•
"Y-Zoom": 1, 2, 5 and 10x signal magnification in "dB"
•
"Unzoom": Reset the presentation to the nominal measuring range
with single magnification
The following circumstances cause interfering reflections and can
influence the measurement:
•
High sockets
•
Vessel installations such as struts
•
Agitators
•
Buildup or welded joints on vessel walls
Note:
A false signal suppression detects, marks and saves these false sig-
nals so that they are no longer taken into account for level measure-
ment.
This should be done with the low level so that all potential interfering
reflections can be detected.
Proceed as follows:
1. Select the menu item "Additional settins" with [->] and confirm
with [OK]. With [->] you have to select the menu item "False
signal suppression" and confirm with [OK].
Diagnoses/Curve indica-
tion
Additional adjustments/
False signal suppression