VEGA VEGABAR 54 Foundation Fieldbus - climate compensated User Manual
Page 9
9
3 Product description
VEGABAR 54 • Foundation Fieldbus - climate compensated
36791-EN-130321
signal, compared with an integrated reference pressure measurement
and outputted as measured value via the output signal.
The CERTEC
®
measuring cell is also equipped with a temperature
sensor. The temperature value can be displayed via the display and
adjustment module or processed via the signal output.
As a standard feature, the CERTEC
®
measuring cell is equipped with
a lateral, recessed seal.
Instruments with double seal have an additional front seal.
Instruments with hygienic fitting are equipped with a gap-free form
seal.
Power is supplied via the H1 Fieldbus. A two-wire cable according to
Fieldbus specification serves as carrier of both power and digital data
for multiple sensors. This cable can be operated in two versions:
•
via an H1 interface card in the control system and additional power
supply
•
via a Linking device with HSE (High speed Ethernet) and addi-
tional power supply according to IEC 61158-2
The DD (Device Descriptions) and CFF (capability files) necessary
for planning and configuration of your FF (Foundation Fieldbus) com-
munication network are available in the download area of the VEGA
homepage www.vega.com under "Services - Downloads - Software
- Foundation Fieldbus". The appropriate certificates are also available
there. A CD with the appropriate files and certificates can be ordered
via e-mail under [email protected] or by phone from one of the
VEGA agencies under the order number "DRIVER.S".
The backlight of the display and adjustment module is powered by the
sensor. Prerequisite is a certain level of operating voltage.
The data for power supply are specified in chapter "Technical data".
The optional heating requires its own operating voltage. You can find
details in the supplementary instructions manual "Heating for display
and adjustment module".
This function is generally not available for approved instruments.
3.3 Operation
The instrument can be adjusted with the following adjustment media:
•
With the display and adjustment module
•
with the suitable VEGA DTM in conjunction with an adjustment
software according to the FDT/DTM standard, e.g. PACTware and
PC
•
a configuration tool
3.4 Packaging, transport and storage
Your instrument was protected by packaging during transport. Its
capacity to handle normal loads during transport is assured by a test
based on ISO 4180.
Seal concept
Power supply and bus
communication
DD/CFF
Packaging