8 Maintenance and fault rectification
VEGABAR 54 • Foundation Fieldbus - climate compensated
36791-EN-130321
•
F
T
: Temperature coefficient (influence of medium or ambient
temperature)
•
F
Kl
: Deviation
•
F
a
: Error current output
Pressure measurement in the pipeline 8 bar (800 KPa)
Product temperature 10 °C, reference temperature 20 °C
Calculation ΔT: ΔT = 20 °C - 10 °C = 10 K
VEGABAR 54 climate compensated, with measuring range 25 bar
Calculation of the set Turn Down: TD = 25 bar/8 bar, TD = 3.1
Basic accuracy digital output signal in percent:
F
perf
= √((F
T
)
2
+ (F
Kl
)
2
)
F
T
= (0.02 + 0.03 x TD)%/10 K
F
Kl
= 0.25 %
F
perf
= √((0.02 + 0.03 x 3.1)%/10 K x10 K)
2
+ (0.25 %)
2
)
F
perf
= 0.27 %
Total deviation digital output signal in percent:
F
total
= F
perf
+ F
stab
F
stab
= (0.1 % x TD)/year
F
stab
= (0.1 % x 3.1)/year
F
stab
= 0.31 %
F
total
= 0.27 % + 0.31 % = 0.58 %
Total deviation digital output signal absolute:
F
total
= 0.58 % x 8 bar/100 % = 46.4 mbar
Basic accuracy analogue output signal in percent:
F
perf
= √((F
T
)
2
+ (F
Kl
)
2
+ (F
a
)
2
)
F
T
= (0.02 + 0.03 x TD)%/10 K
F
Kl
= 0.25 %
F
a
= 0.15 %
F
perf
= √((0.02 + 0.03 x 3.1)%/10 K x10 K)
2
+ (0.25 %)
2
) + (0.15 %)
2
)
F
perf
= 0.31 %
Total deviation analogue output signal in percent:
F
total
= F
perf
+ F
stab
F
stab
= (0.1 % x TD)/year
F
stab
= (0.1 % x 3.1)/year
F
stab
= 0.31 %
F
total
= F
perf
+ F
stab
= 0.31 % + 0.31 % = 0.62 %
Total deviation analogue output signal absolute:
F
total
= 0.62 % x 8 bar/100 % = 49.6 mbar
Example