6 Set up with the display and adjustment module

VEGAPULS SR 68 • Foundation Fieldbus

38297-EN-130624

When a reset is carried out, all settings (with only a few exceptions)

are reset. The exceptions are: PIN, language, lighting, SIL and HART

mode.

The following reset functions are available:

Delivery status: Restoring the parameter settings at the time

of shipment from the factory. A created false signal suppression,

user-programmable linearization curve, measured value memory

as well as event memory will be deleted.

Basic settings: Resetting of the parameter settings incl. special

parameters to the default values of the respective instrument. Any

created false signal suppression, user programmable linearization

curve, measured value memory as well as event memory will be

deleted.

Setup: Resetting of the parameter settings to the default values of

the respective instrument . Order-related settings remain but are

not taken over into the current parameters. User-generated false

signal suppression, user-programmed linearization curve, meas-

ured value memory, echo curve memory as well as event memory

remain untouched. The linearization is set to linear.

False signal suppression: Deleting a previously created false

signal suppression. The false signal suppression created in the

factory remains active.

Peak values measured value: Resetting of the measured min.

and max. distances to the actual measured value.

Select the requested reset function [->] and confirm with [OK].
The following table shows the default values of VEGAPULS SR 68:

Menu section

Menu item

Default value

Setup

Measurement

loop name

Sensor

Medium

Liquid/Water
Bulk solids/Crushed stones, gravel

Application

Storage tank
Silo

Vessel form

Vessel bottom, dished boiler end
Vessel top, dished boiler end

Vesell height/

Measuring range

Recommended measuring range, see

"Technical data" in the supplement

Min. adjustment

Recommended measuring range, see

"Technical data" in the supplement

Damping

0.0 s

Additional adjustments

- Reset