VEGA VEGAPULS SR 68 Foundation Fieldbus User Manual
Page 51
51
6 Set up with the display and adjustment module
VEGAPULS SR 68 • Foundation Fieldbus
38297-EN-130624
When a reset is carried out, all settings (with only a few exceptions)
are reset. The exceptions are: PIN, language, lighting, SIL and HART
mode.
The following reset functions are available:
•
Delivery status: Restoring the parameter settings at the time
of shipment from the factory. A created false signal suppression,
user-programmable linearization curve, measured value memory
as well as event memory will be deleted.
•
Basic settings: Resetting of the parameter settings incl. special
parameters to the default values of the respective instrument. Any
created false signal suppression, user programmable linearization
curve, measured value memory as well as event memory will be
deleted.
•
Setup: Resetting of the parameter settings to the default values of
the respective instrument . Order-related settings remain but are
not taken over into the current parameters. User-generated false
signal suppression, user-programmed linearization curve, meas-
ured value memory, echo curve memory as well as event memory
remain untouched. The linearization is set to linear.
•
False signal suppression: Deleting a previously created false
signal suppression. The false signal suppression created in the
factory remains active.
•
Peak values measured value: Resetting of the measured min.
and max. distances to the actual measured value.
Select the requested reset function [->] and confirm with [OK].
The following table shows the default values of VEGAPULS SR 68:
Menu section
Menu item
Default value
Setup
Measurement
loop name
Sensor
Medium
Liquid/Water
Bulk solids/Crushed stones, gravel
Application
Storage tank
Silo
Vessel form
Vessel bottom, dished boiler end
Vessel top, dished boiler end
Vesell height/
Measuring range
Recommended measuring range, see
"Technical data" in the supplement
Min. adjustment
Recommended measuring range, see
"Technical data" in the supplement
Damping
0.0 s
Additional adjustments
- Reset