Quick start – VEGA VEGAPULS SR 68 Foundation Fieldbus User Manual

Page 2

background image

2

Quick start

VEGAPULS SR 68 • Foundation Fieldbus

38297-EN-130624

Quick start

The quick start procedure enables a quick setup with many applica-

tions. You can find further information in the respective chapters of the

operating instructions manual.
1. Distance from the vessel wall > 200 mm, the antenna should

protrude > 10 mm into the vessel

ca

. 10 mm

200 mm

(7.87")

Fig. 1: Distance of the antenna to the vessel wall/vessel ceiling

2. Note min. socket diameter depending on the socket length
3. Note the instructions for sealing
For further information see chapter "Mounting".
1. Make sure that the power supply corresponds to the specifica-

tions on the type label.

2. Connect the instrument according to the following illustration

1

2

( )

(-)

1

5

0

1

0

1

+

6 7 8

Bus

2
3

4

5

Fig. 2: Electronics and connection compartment, single chamber housing
1 Voltage supply, signal output

2 Contact pins for the display and adjustment module or interface adapter

3 Simulation switch ("1" = mode for simulation release)

4 For external display and adjustment unit

5 Ground terminal for connection of the cable screen

For further information see chapter "Connecting to power supply".
1. Go via the display and adjustment module to the menu "Setup".

2. Select in the menu item "Medium" the medium of your applica-

tion, for example "Powder/Dust".

Mounting

Electrical connection

Set parameters