4 Mounting
VEGAPULS SR 68 • Foundation Fieldbus
38297-EN-130624
4 Mounting
4.1 General instructions
On instruments with process fitting thread, the hexagon must be tight-
ened with a suitable screwdriver. Wrench size see chapter "Dimen-
sions".
Warning:
The housing must not be used to screw the instrument in! Applying
tightening force can damage internal parts of the housing.
Protect your instrument further through the following measures
against moisture penetration:
•
Use the recommended cable (see chapter "Connecting to power
supply")
•
Tighten the cable gland
•
Loop the connection cable downward in front of the cable gland
This applies particularly to:
•
Outdoor mounting
•
Installations in areas where high humidity is expected (e.g. through
cleaning processes)
•
Installations on cooled or heated vessels
Make sure that all parts of the instrument exposed to the process are
suitable for the existing process conditions.
These are mainly:
•
Active measuring component
•
Process fitting
•
Process seal
Process conditions are particularly:
•
Process pressure
•
Process temperature
•
Chemical properties of the medium
•
Abrasion and mechanical influences
You can find the specifications of the process conditions in chapter
"Technical data" as well as on the nameplate.
4.2 Mounting preparations - Horn antenna
The instrument is also available in versions with an antenna whose
diameter is larger than the process fitting (thread, flange). In such
cases the antenna must be disconnected from the process fitting
before mounting. Proceed as follows:
1. Loosen the hexagon socket screws (3) on the antenna socket
with an Allen wrench (size 3)
2. Remove the antenna (4)
Note:
The plastic cone may not be pulled out of the antenna socket.
Screwing in
Protection against mois-
ture
Suitability for the process
conditions