8 Maintenance and fault rectification
PLICSMOBILE T61 • External GSM/GPRS radio unit
37700-EN-130228
8 Maintenance and fault rectification
8.1 Maintenance
If the instrument is used properly, no special maintenance is required
in normal operation.
8.2 Rectify faults
The operator of the system is responsible for taking suitable meas-
ures to rectify faults.
A maximum of reliability is ensured. Nevertheless, faults can occur
during operation. These may be caused by the following, e.g.:
•
Measured value from sensor not correct
•
Voltage supply
•
Interference on the cables
The first measures to be taken are to check the input/output signals
as well as to evaluate the error messages via the DTM. The procedure
is described below. In many cases, the causes can be determined in
this way and faults can be rectified.
Should these measures not be successful, please call in urgent cases
the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is available to you 7 days a week round-the-clock. Since
we offer this service world-wide, the support is only available in the
English language. The service is free of charge, only the standard
telephone costs will be charged.
Error code Cause
Rectification
No indication
of the signal
strength
No GSM network
available
– Check network availability via mobile
phone
E008
Sensor not found
– Check connection of the sensor
E013
Sensor signals
failure, no valid
measured value
– Check sensor parameter adjustment
– Send sensor for repair
E030
Sensor in boot phase
value not valid
– Check sensor parameter adjustment
E034
EEPROM CRC error
– Switch the instrument off and on
– Carry out a reset
– Send instrument for repair
E035
ROM CRC error
– Switch the instrument off and on
– Carry out a reset
– Send instrument for repair
E036
Instrument software
not executable (dur-
ing software update
or after failed update)
– Wait until software update is finished
– Carry out another software update
Reaction when malfunc-
tions occur
Failure reasons
Fault rectification
24 hour service hotline
Error messages