6 Set up with the display and adjustment module

VEGAPULS SR 68 • 4 … 20 mA/HART two-wire

38294-EN-130624

Enter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [ESC] and [->] key.
Caution:

Note the following if the instrument with corresponding approval is

used as part of an overfill protection system according to WHG:
If a linearization curve is selected, the measuring signal is no longer

necessarily linear to the filling height. This must be considered by the

user especially when adjusting the switching point on the limit signal

transmitter.

With a reset, certain parameter adjustments carried out by the user

are reset.

The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of ship-

ment from the factory incl. the order-specific settings. A created false

signal suppression, user-programmable linearization curve as well as

the measured value memory will be deleted.
Basic settings: Resetting the parameter settings incl. special pa-

rameters to the default values of the respective instrument. A created

false signal suppression, user programmable linearization curve as

well as the measured value memory will be deleted.
Setup: Resetting of the parameter settings to the default values of the

respective instrument in the menu item Setup. User-generated false

signal suppression, user-programmed linearization curve, measured

value memory as well as event memory remain untouched. The

linearization is set to linear.
False signal suppression: Deleting a previously created false signal

suppression. The false signal suppression created in the factory

remains active.
Peak values measured value: Resetting of the measured min. and

max. distances to the actual measured value.
The following table shows the default values of the instrument. De-

pending on the instrument version, not all menu items are available or

differently assigned:

Additional adjustments

- Reset