6 Set up with the display and adjustment module
VEGAPULS SR 68 • 4 … 20 mA/HART two-wire
38294-EN-130624
The following circumstances cause interfering reflections and can
influence the measurement:
•
High sockets
•
Vessel installations such as struts
•
Agitators
•
Buildup or welded joints on vessel walls
Note:
A false signal suppression detects, marks and saves these false sig-
nals so that they are no longer taken into account for level measure-
ment.
This should be done with the low level so that all potential interfering
reflections can be detected.
Proceed as follows:
1. Select the menu item "Additional settins" with [->] and confirm
with [OK]. With [->] you have to select the menu item "False
signal suppression" and confirm with [OK].
2. Confirm again with [OK].
3. Confirm again with [OK].
4. Confirm again with [OK] and enter the actual distance from the
sensor to the product surface.
5. All interfering signals in this section are detected by the sensor
and stored after confirming with [OK].
Note:
Check the distance to the product surface, because if an incorrect
(too large) value is entered, the existing level will be saved as a false
echo. The filling level would then no longer be detectable in this area.
Additional adjustments -
False signal suppression