11 Supplement

VEGAPULS 63 • HART and accumulator pack

40794-EN-130228

3

4

2

1

Fig. 40: Data of the input variable
1 Reference plane

2 Measured variable, max. measuring range

3 Length antenna cone

4 Useful measuring range

Standard electronics
Max. measuring range

35 m (114.8 ft)

Recommended measuring range

Ʋ Flange DN 50, 2"

up to 15 m (49.21 ft)

Ʋ Flange DN 80, 3"

up to 35 m (114.8 ft)

Electronics with increased sensitivity
Max. measuring range

75 m (246.1 ft)

Flange DN 50, 2"

up to 15 m (49.21 ft)

Flange DN 80, 3"

up to 35 m (114.8 ft)

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Installation reference conditions

Ʋ Min. distance to installations

> 200 mm (7.874 in)

Ʋ Reflector

Plane plate reflector

Ʋ False reflections

Biggest false signal, 20 dB smaller than the useful signal

Deviation with liquids

See following diagrams