VEGA VEGAPULS 63 (≥ 2.0.0 - ≥ 4.0.0) HART and accumulator pack User Manual
Page 38
38
6 Set up with the display and adjustment module
VEGAPULS 63 • HART and accumulator pack
40794-EN-130228
by the user, particularly when setting the switching point on the limit
signal indicator.
When a reset is carried out, all settings (with only a few exceptions)
are reset. The exceptions are: PIN, language, lighting, SIL and HART
mode.
The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of ship-
ment from the factory incl. the order-specific settings. A created false
signal suppression, user-programmable linearization curve as well as
the measured value memory will be deleted.
Basic settings: Resetting the parameter settings incl. special and
laboratory parameters to the default values of the respective instru-
ment. A created false signal suppression, user programmable lineari-
zation curve as well as the measured value memory will be deleted.
Setup: Resetting of the parameter settings to the default values of the
respective instrument in the menu item Setup. User-generated false
signal suppression, user-programmed linearization curve, measured
value memory as well as event memory remain untouched. The
linearization is set to linear.
False signal suppression: Deleting a previously created false signal
suppression. The false signal suppression created in the factory
remains active.
Peak values distance: Resetting the measured min. and max. dis-
tances to the actual measured value.
The following table shows the default values of the instrument. De-
pending on the instrument version, not all menu items are available or
differently assigned:
Additional adjustments
- Reset