beautypg.com

VEGA VEGAPULS 63 (≥ 2.0.0 - ≥ 4.0.0) HART and accumulator pack User Manual

Page 36

background image

36

6 Set up with the display and adjustment module

VEGAPULS 63 • HART and accumulator pack

40794-EN-130228

changes over the operating time. In addition, the echo curve of the

setup can be also displayed in the echo curve window and compared

with the actual echo curve.

The following circumstances cause interfering reflections and can

influence the measurement:

High sockets

Vessel installations such as struts

Agitators

Buildup or welded joints on vessel walls

Note:

A false signal suppression detects, marks and saves these false sig-

nals so that they are no longer taken into account for level measure-

ment.
This should be done with the low level so that all potential interfering

reflections can be detected.
Proceed as follows:
1. Select the menu item "Additional settins" with [->] and confirm

with [OK]. With [->] you have to select the menu item "False

signal suppression" and confirm with [OK].

2. Confirm again with [OK].

3. Confirm again with [OK].

4. Confirm again with [OK] and enter the actual distance from the

sensor to the product surface.

5. All interfering signals in this section are detected by the sensor

and stored after confirming with [OK].

Additional adjustments -

False signal suppression