7 Setup with PACTware
VEGAPULS WL 61 • 4 … 20 mA/HART - two-wire
38061-EN-121011
If these values are not known, an adjustment with the distances of for
example 10 % and 90 % is possible. Starting point for these distance
specifications is always the seal surface of the thread or flange. By
means of these settings, the real level will be calculated.
The real product level during this adjustment is not important, be-
cause the min./max. adjustment is always carried out without chang-
ing the product level. These settings can be made ahead of time
without the instrument having to be installed.
All device DTMs are available as a free-of-charge standard version
and as a full version that must be purchased. In the standard version,
all functions for complete setup are already included. An assistant for
simple project configuration simplifies the adjustment considerably.
Saving/printing the project as well as import/export functions are also
part of the standard version.
In the full version there is also an extended print function for complete
project documentation as well as a save function for measured value
and echo curves. In addition, there is a tank calculation program as
well as a multiviewer for display and analysis of the saved measured
value and echo curves.
The standard version is available as a download under www.vega.
com/downloads and "Software". The full version is available on CD
from the agency serving you.
7.3 Saving the parameter adjustment data
We recommend documenting or saving the parameter adjustment
data via PACTware. That way the data are available for multiple use or
service purposes.
Standard/Full version