5 Connecting to power supply

VEGAPULS WL 61 • 4 … 20 mA/HART - two-wire

38061-EN-121011

5 Connecting to power supply

5.1 Preparing the connection

Always keep in mind the following safety instructions:

Connect only in the complete absence of line voltage

If overvoltage surges are expected, overvoltage arresters should

be installed

Power supply and current signal are carried on the same two-wire

cable. The voltage supply range can differ depending on the instru-

ment version.
The data for power supply are specified in chapter "Technical data".
Provide a reliable separation between the supply circuit and the

mains circuits according to DIN VDE 0106 part 101.
Keep in mind the following additional factors that influence the operat-

ing voltage:

Output voltage of the power supply unit can be lower under nomi-

nal load (with a sensor current of 20.5 mA or 22 mA in case of fault

message)

Influence of additional instruments in the circuit (see load values in

chapter "Technical data")

The instrument is connected with standard two-wire cable without

screen. If electromagnetic interference is expected which is above the

test values of EN 61326-1 for industrial areas, screened cable should

be used.
For instruments with housing and cable gland, use cable with round

cross-section. A cable outer diameter of 5 … 9 mm (0.2 … 0.35 in)

ensures the seal effect of the cable gland. If you are using cable with

a different diameter, exchange the seal or use a suitable cable gland.
We generally recommend the use of screened cable for HART multi-

drop mode.

5.2 Wiring plan

1

2

Fig. 23: Wire assignment fix-connected connection cable
1 brown (+) and blue (-) to power supply or to the processing system

2 Shielding

5.3 Switch-on phase

After connecting the instrument to power supply or after a voltage

recurrence, the instrument carries out a self-check for approx. 30 s:

Safety instructions

Voltage supply

Connection cable

Wire assignment, con-