3 shorten suspension cable, 4 shorten suspension cable – VEGA VEGAWELL 52 4 … 20 mA User Manual
Page 22
à Check the pressure compensation and clean the filter
element, if necessary
?
4 … 20
mA signal missing
l
W
rong connection to voltage supply
à Check connection according to chapter "Connection steps"
and if necessary, correct according to chapter "Wiring plan"
l
N
o power supply
à Check cables for breaks; repair if necessary
l
O
perating voltage too low or load resistance too high
à Check, adapt if necessary
I
n Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.
D
epending on the reason for the fault and the measures taken, the
steps described in chapter "Set up" may have to be carried out again.
6
.3 Shorten suspension cable
S
horten the suspension cable individually. Proceed as follows:
1
R
emove the filter adapter from the transparent capillary line
2
C
ut the suspension cable with an edge cutter to the requested
length
Caution:
D
o not squeeze the capillary cable, this will influence the pressure
compensation. If necessary, rework with a sharp knife.
3
R
emove approx. 10 cm of the cable mantle, strip off approx. 1 cm
of the wire ends
I
nsert the filter adapter
T
he work steps are finished.
6
.4 Shorten suspension cable
T
he suspension cable can be shortened individually. For the version
with plastic or stainless steel housing proceed as follows:
1
U
nscrew the housing cover
2
L
oosen the screw terminals and remove the wire ends of the
suspension cable out of the screw terminals
3
H
old the hexagon on the screwed socket with SW 46 and loosen
with seal screw SW 22
Caution:
S
eal screw is secured with Loctide pink, mote breakaway torque!
Reaction after fault rec-
tification
22
VEGAWELL
52 • 4 … 20
mA
6 M
aintenance and fault rectification