VEGA VEGAFLEX 66 (-110…+400°C) Profibus PA User Manual
Page 29
Keep in mind that interfaces can cause faulty measurements.
If you want to measure the total height of both liquids reliably,
please contact our service department or use an instrument
specially designed for interface measurement.
Start your parameter adjustment with the following menu items
of the basic adjustment:
Proceed as follows:
1 Move from the measured value display to the main menu
by pushing [OK].
▶
Basic adjustment
Display
Diagnostics
Service
Info
2 Select the menu item "Basic adjustment" with [->] and
confirm with [OK]. Now the menu item "Min. adjustment" is
displayed.
Min. adjustment
0.00 %
=
10.000 m(d)
8.000 m(d)
3 Prepare the % value for editing with [OK] and set the
cursor to the requested position with [->]. Set the
requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
4 Enter the suitable distance value in m for the empty vessel
(e.g. distance from the sensor to the vessel bottom)
corresponding to the percentage value.
5 Save the settings with [OK] and move to "Max. adjustment"
with [->].
Proceed as follows:
Max. adjustment
100.00 %
=
1.000 m(d)
2.000 m(d)
1 Prepare the % value for editing with [OK] and set the
cursor to the requested position with [->]. Set the
requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
Carrying out min. ad-
justment
Carrying out max. ad-
justment
VEGAFLEX
66 • Profibus PA
29
6 Set up with the indicating and adjustment module PLICSCOM