3 function chart – VEGA VEGACAP 27 - Relay (DPDT) User Manual
Page 15
15
6 Setup
VEGACAP 27 • - Relay (DPDT)
33758-EN-130916
3. Turn the below potentiometer (6) first of all anticlockwise (max. 20
turns) until the control lamp signals "covered".
Mode A (overfill protection) = control lamp lights
Mode B (dry run protection) = control lamp extinguishes
If this condition is already reached, you can continue with the next
step.
4. Turn the potentiometer (6) very slowly (due to the damping) clock-
wise until the control lamp signals "uncovered".
Mode A (overfill protection) = control lamp extinguishes
Mode B (dry run protection) = control lamp lights
5. Turn the potentiometer (6) clockwise according to the following
chart.
6. The probe is now ready for operation.
Sensitivity
Standard
very sensitive
additional turns
Dielectric constant >2
= 2 turns
Dielectric constant >1.5
= 1 turn
Tab. 1: Number of additional turns for the potentiometer (6)
Note:
With the measurement of products with very low dielectric values, the
number of turns can be reduced up to 1 according to the chart.
This setting is too sensitive with conductive, adhesive products.
Note:
When placing the housing cover, make sure that the inspection glass
is above the signal lamp of the electronics module.
6.3 Function chart
The following chart provides an overview of the switching conditions
depending on the set mode and the level.
Level
Switching status Control lamp
Mode A
Overflow protec-
tion
5
3
4
(8)
(6) (7)
Relay energized
Mode A
Overflow protec-
tion
5
3
4
(8)
(6) (7)
Relay deener-
gized