2 mounting instructions – VEGA VEGACAP 27 - Relay (DPDT) User Manual
Page 11
11
4 Mounting
VEGACAP 27 • - Relay (DPDT)
33758-EN-130916
The process fitting must be sealed if there is gauge or low pressure in
the vessel. Before use, check if the seal material is resistant against
the measured product and the process temperature.
The max. permissible pressure is specified in chapter "Technical
data" or on the type label of the sensor.
4.2 Mounting instructions
Due to the effects of agitators, equipment vibration or similar, the level
switch can be subjected to strong lateral forces. For this reason, do
not use an overly long electrode for VEGACAP 27, but check if you
can mount a short level switch on the side of the vessel in horizontal
position.
Extreme vibration caused by the system, e.g. due to agitators or
turbulence in the vessel from fluidisation, can cause the probe of
VEGACAP 27 to vibrate in resonance. If a longer rod version is neces-
sary, you can secure the probe by fastening a suitable brace or guy
directly above the end of the rod.
If the instrument is mounted in the filling stream, unwanted false
measurement signals can be generated. For this reason, mount the
instrument at a position in the vessel where no disturbances, e.g. from
filling openings, agitators, etc., can occur.
This applies particularly to instrument versions with a longer probe.
Fig. 4: Inflowing medium
Pressure/Vacuum
Agitators and fluidization
Inflowing medium