beautypg.com

VEGA VEGAFLEX 66 (-20…+250°C) Foundation Fieldbus User Manual

Page 56

background image

-

Min./Max. adjustment: this is the value of level at "Calibration Lowest Point". The unit is
defined in "level_unit"

-

When writing "cal_level_lo" and "cal_type" = 1, the "Calibration Lowest Point" is automatically set
to "sensor_value"

l

cal_type

-

Min./Max. adjustment: this parameter defines the type of calibration:

-

Dry: no influence of "sensor_value" on level calibration

-

Online: current "sensor_value"determines "Calibration Highest/Lowest Point"

l

level

l

level_unit

l

level_offset

l

sensor_offset

l

end_of_operation_range

l

begin_of_operation_range

l

product_type

-

set up to suit the process conditions

l

liquids_medium_type

-

set up to suit the process conditions

l

solids_medium_type

-

set up to suit the process conditions

l

liquids_vessel_type

-

set up to suit the process conditions

l

solids_vessel_type

-

set up to suit the process conditions

l

fast_level_change

-

set up to suit the process conditions

l

first_echo_factor

l

pulse_velocity_correction

l

echo_quality

l

empty_vessel_curve_corr_dist

-

The actual distance from sensor to the product surface must be entered before creating a
false echo memory

-

The unit is defined in "sensor_range.Units Index"

l

empty_vessel_curve_corr_op_code

-

Create a false echo memory. Selectable codes are: update, create new and delete

l

total_sensor_value

56

VEGAFLEX

66 • Foundation Fieldbus

10 Supplement

34172

-EN

-100426