VEGA VEGAFLEX 66 (-20…+250°C) Foundation Fieldbus User Manual
Page 46
Current value
10 mA, ±0.5 mA
Resolution, digital
> 1
mm (0.039 in)
Accuracy (similar to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1
-
Temperature
+18
… +30 °C (+64 … +86 °F)
-
Relative humidity
45 … 75 %
-
Air pressure
+860
… +1060 mbar/+86 … +106 kPa
(+12.5 … +15.4 psig)
Installation reference conditions
-
Min. distance to installations
> 500
mm (19.69 in)
-
Vessel
metallic, ø 1 m (3.281 ft), centric installation,
process fitting flush with the vessel ceiling
-
Medium
Water/Oil (Dk value ~2.0)
-
Installation
Probe end does not touch the vessel bottom
Sensor parameter adjustment
Gating out of false signals carried out
In bulk solids applications, implementing a false
signal suppression is generally not recommended.
The accuracy of bulk solid applications depends
considerably on the application. Hard and fast
accuracy specifications are thus not available.
Deviation
see diagrams
Depending on the installation conditions, there can
be deviations which can be rectified with an
adaptation of the adjustment or a change of the
measured value offset in the DTM service mode.
46
VEGAFLEX
66 • Foundation Fieldbus
10 Supplement
34172
-EN
-100426