VEGA VEGAFLEX 66 (-20…+250°C) Foundation Fieldbus User Manual
Page 52
Voltage supply
Operating voltage
-
Non-Ex instrument
9 … 32 V DC
-
EEx-ia instrument
9 … 24 V DC
-
EEx-d instrument
16 … 32 V DC
Operating voltage with lighted indicating and adjustment module
-
Non-Ex instrument
12 … 32 V DC
-
EEx-ia instrument
12 … 24 V DC
-
EEx-d instrument
20 … 32 V DC
Power supply by/max. number of sensors
-
H
1 power supply
max. 32 (max. 10 with Ex)
Electrical protective measures
Protection, depending on housing version
-
Plastic housing
IP
66/IP 67
-
Aluminium housing, stainless steel
housing - investment casting, stainless
steel housing - electro-polished
IP
66/IP 68 (0.2 bar)
5)
-
Aluminium and stainless housing, in-
vestment casting (optionally available)
IP
66/IP 68 (1 bar)
Overvoltage category
III
Protection class
II
Approvals
Depending on the version, instruments with approvals can have different technical data.
For these instruments, the corresponding approval documents have to be taken into account.
These are part of the delivery or can be downloaded under www.vega.com via "VEGA Tools" and
"
serial number search" as well as via "Downloads" and "Approvals".
5)
A suitable cable is the prerequisite for maintaining the protection rating.
52
VEGAFLEX
66 • Foundation Fieldbus
10 Supplement
34172
-EN