beautypg.com

VEGA VEGABAR 63 Foundation Fieldbus User Manual

Page 54

background image

Input variable

Adjustment

Adjustment range of the min./max. adjustment relating to the nominal measuring range:

-

Min.

-5 … +95 %

-

Max.

-5 … +105 %

Adjustment range of the zero/span adjustment relating to the nominal measuring range:

-

zero

-5 … +95 %

-

Span

-5 … +105 %

Recommended max. turn down

10 : 1 (no limitation)

Nominal measuring ranges and overload resistance

Nominal range

Overload, max. pressure Overload, min. pressure

Gauge pressure

0 … 0.4 bar/0 … 40 kPa

2 bar/200 kPa

-1 bar/-100 kPa

0 … 1.6 bar/0 … 160 kPa

10 bar/1000 kPa

-1 bar/-100 kPa

0 … 16 bar/0 … 1.6 MPa

80 bar/8 MPa

-1 bar/-100 kPa

0 … 40 bar/0 … 4 MPa

80 bar/8 MPa

-1 bar/-100 kPa

0 … 100 bar/0 … 10 MPa

200 bar/20 MPa

-1 bar/-100 kPa

0 … 250 bar/0 … 25 MPa

500 bar/50 MPa

-1 bar/-100 kPa

0 … 600 bar/0 … 60 MPa

1200 bar/120 MPa

-1 bar/-100 kPa

-1 … 3 bar/-100 … 300 kPa

17 bar/1700 kPa

-1 bar/-100 kPa

-1 … 5 bar/-100 … 500 kPa

35 bar/3500 kPa

-1 bar/-100 kPa

-1 … 15 bar/-100 … 1.5 MPa

80 bar/8 MPa

-1 bar/-100 kPa

Absolute pressure

0 … 0.4 bar/0 … 40 kPa

2 bar/200 kPa

0 bar abs.

0 … 1.6 bar/0 … 160 kPa

10 bar/1000 kPa

0 bar abs.

0 … 6 bar/0 … 600 kPa

35 bar/3500 kPa

0 bar abs.

0 … 16 bar/0 … 1.6 MPa

80 bar/8 MPa

0 bar abs.

Reference conditions and actuating variables (similar to DIN EN 60770-1)

Reference conditions according to DIN EN 61298-1

-

Temperature

+

18 … +30 °C (+64 … +86 °F)

-

Relative humidity

45 … 75 %

-

Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Determination of characteristics

Limit point adjustment according to IEC 61298-2

Characteristics

linear

Reference installation position

upright, diaphragm points downward

Influence of the installation position

depending on the isolating diaphragm version

54

VEGABAR

63 • Foundation Fieldbus

10 Supplement

32464

-EN

-081209