beautypg.com

VEGA VEGABAR 63 Foundation Fieldbus User Manual

Page 39

background image

Zero adjustment

000.0 %

P

=

+0000

.0 mbar

0000.0 mbar

2

Set the requested mbar value with [+] and [->].

3

Confirm with [+] and move to span adjustment with [->].

The zero adjustment is finished.

Information:
The zero adjustment shifts the value of the span adjustment. The span,
i.e. the difference between these values, however, remains un-
changed.

Information:
For an adjustment with pressure, you simply enter the displayed actual
measured value. If the adjustment ranges are exceeded, the message
"O

utside parameter limits" appears. The editing procedure can be

aborted with [ESC] or the displayed limit value can be accepted with
[OK]

.

Proceed as follows:

1

Edit the mbar value in the menu item "span" with [OK].

Span adjustment

100.0 %

P

=

+1000

.0 mbar

0000.0 mbar

Information:
The displayed pressure for 100 % corresponds to the nominal
measuring range of the sensor (in the above example 1 bar =
1000 mbar).

2

Set the requested mbar value with [->] and [OK].

3

Confirm with [OK] and move to the menu overview with [ESC].

The span adjustment is finished.

Information:
For an adjustment with pressure, you simply enter the displayed actual
measured value. If the adjustment ranges are exceeded, the message
"O

utside parameter limits" appears. The editing procedure can be

aborted with [ESC] or the displayed limit value can be accepted with
[OK]

.

Carrying out span ad-
justment

VEGABAR

63 • Foundation Fieldbus

39

6 Set up with the indicating and adjustment module PLICSCOM

32464

-

EN

-081209