VEGA VEGABAR 63 Foundation Fieldbus User Manual
Page 35
The adjustment unit is hence switched over from bar to m.
Proceed as follows to select the temperature unit:
5)
à Activate the selection with [OK] and select "Temperature unit
with [->].
à Activate the selection with [OK] and select the requested unit with
[->]
(e.g. °F).
à Confirm with [OK].
The temperature unit is hence switched over from °C to °F.
Proceed as follows:
1
Activate in the menu item "Position correction" the selection with
[OK]
.
Position correction
Offset
P
=
+
0000 mbar
53 mbar
2
Select with [->], e.g. to accept actual measured value.
Position correction
Accept current measured
value?
▶
Accept
Edit
3
Confirm with [OK] and move to min.(zero) adjustment with [->].
Proceed as follows:
1
Edit the % value in the menu item "Min. adjustment" with [OK].
Min. adjustment
+000
.0 %
=
+0000
.0 mbar
0000.0 mbar
2
Set the requested percentage value with [+] and [->].
3
Edit the requested mbar value with [OK].
4
Set the requested mbar value with [+] and [->].
5
Confirm with [+] and move to max. adjustment with [->].
The min. adjustment is finished.
Information:
For an adjustment with filling, you simply enter the displayed actual
measured value. If the adjustment ranges are exceeded, the message
"O
utside parameter limits" appears. The editing procedure can be
5)
Selection options: °C, °F.
Carry out position cor-
rection
Carrying out min. ad-
justment
VEGABAR
63 • Foundation Fieldbus
35
6 Set up with the indicating and adjustment module PLICSCOM
32464
-
EN
-081209